Title: | Cox proportional hazards model used for predictive analysis of the energy consumption of healthcare buildings |
Authors: | González-Domínguez, Jaime Sánchez-Barroso, G Sanz-Calcedo, J de Sousa Neves, N |
Keywords: | Cox proportional hazard model Primary healthcare centre Energy consumption Semi-parametric model Sustainability Healthcare engineering |
Issue Date: | 2022 |
Publisher: | Energy and Buildings |
Citation: | González-Domínguez, J., Sánchez-Barroso, G., Sanz-Calcedo, J., de Sousa Neves, N. (2022) Cox proportional hazards model used for predictive analysis of the energy consumption of healthcare buildings, Energy and Buildings 257:111784, https://DOI: 10.1016/j.enbuild.2021.111784 (Factor de impacto: 7.13) |
Abstract: | The energy consumption of healthcare buildings is very high due to their 24/7 functioning and the
demand of electro-medical equipment. This excessive energy consumption cannot be attributed to a
single factor. The objective of this research was to apply Cox proportional hazards model to predict
the probability of energy overconsumption in healthcare buildings for different functional variables. A
reference energy consumption index was established from a retrospective analysis of the monthly consumption
of 64 healthcare buildings during the period 2015–2019. Functional parameters (construction,
facilities, demographics, and climate) were selected as candidates for Cox proportional hazards model.
The study found that the variables related to facilities and demographics significantly influence the
semi-parametric model of energy consumption. Their influence was quantified, and the validity of the
proposed model was verified graphically. Having more than 10,000 users was found to result in a
124% greater probability of exceeding the reference energy consumption, 97.4% greater with an installed
power above 60 kW, and 94.6% greater if the town in which the healthcare building is located has more
than 5000 inhabitants, and 69.4% greater if a heat pump is not used for air-conditioning. The Cox proportional
hazards model was shown to be an advanced tool useful for quantifying the influence of various
functional variables on the excess energy consumption of healthcare buildings. The results of the research
generate objective information to establish, on the one hand, criteria for designing and renovating healthcare
buildings and, on the other hand, care planning strategies. |